compli 310 E
JP50077Mechanical data | |
---|---|
Pump | Vertical single-stage |
Free passage | 50 mm |
Pressure pipe | DN 80 |
Shaft | Stainless steel |
Impeller | Vortex impeller, stainless steel |
Motor housing | Stainless steel |
Pump housing | Grey cast iron |
Submersible | Yes |
Pressure outlet | DN 80 |
Tank capacity | 50 l |
Weight | 31 kg |
Electrical data | |
---|---|
Voltage | 1/N/PE~230 V |
Motor rating P1 | 1.2 kW |
Motor rating P2 | 0.98 kW |
Current | 4.5 A |
Power line | 4m H07RN-F |
Wires | 4G1,0 |
Type of enclosure | IP 68 |
Insulation class | F |
Winding thermostat | Yes |
Plug | Safety |

Performance | ||||||
---|---|---|---|---|---|---|
Delivery head H [m] | 1 | 2 | 3 | 4 | 5 | 6 |
Flow rate Q [m³/h] | 30 | 27 | 23 | 19 | 15 | 11 |
Specifications can be changed without notice. Performance subject to ISO 9906 tolerances.
The minimum flow velocity in the pressure piping must be 0.7 m/s according to EN 12056.
This data is represented in the performance curve as a limit of application.



The compli has a DN 80/PN 4 outlet flange. The following stop valve and pipework are installed in DN 80.
In keeping with the construction and testing principles of European standard EN 12050, sewage lifting stations are to be used for the transport of faecal matter and domestic wastewater in building drainage systems as described in German standard DIN 1986 T3. In keeping with the stipulations of European standard EN 12056-4 they have to be mounted with collecting tanks inside building permitting a free space of 60 cm for operation and repair. The pressure pipe has to be passed above the locally defined backpressure level and a non-return valve tested in keeping with European standard 12050-4 has to be mounted. In keeping with European standard 12056 the ventilation pipe has to be passed up to the roof.
Attention! The inlet pipes of the lowlateral inlets must be euipped with a dam loop. This loop must have at least a height of 180 mm between ground and invert. The feed line must be ventilated on its highest elevation.
Mechanical accessory | ||||||
---|---|---|---|---|---|---|
Code No. | ||||||
Inlet gate valve PVC | ||||||
with two pipe sockets, DN 100, PN1 | 360x295 (HxW) | JP28297 | ||||
Sluice valve | ||||||
DN 80, PN 10, EN 1171 | 315x180 (HxB) | JP00639 | ||||
Hand diaphragm pump | ||||||
for emergency purposes (up to Hgeo 15 m) | 640x1½” (HxD) | JP00255 | ||||
Stop valve | ||||||
brass, 1½“ (DN 40), PN 16 | 125x60 (HxB) | JP44786 | ||||
Elastic connection | ||||||
1½“ (DN 40), PN 4 | 120x50 (HxD) | JP44777 | ||||
Connection kit | ||||||
DN 100 | D=110 | JP42910 |
Electrical accessory | ||||||
---|---|---|---|---|---|---|
Code No. | ||||||
Alarm unit | ||||||
AGR | reed switch, mains dependent, potential-free contact, 4 m cable | JP44893 | ||||
Rechargeable battery | ||||||
9 V, for mains independent alarm | JP44850 | |||||
Smart Home | ||||||
FTJP radio transmitter | JP47209 |