JP50096| Mechanical data | |
|---|---|
| Pump | Vertical single-stage |
| Free passage | 7 mm |
| Pressure pipe | DN 40 |
| Bearing | Ball bearings, grease-lubricated |
| Oil chamber | Yes |
| Run dry protection | Yes |
| Shaft | voll gegen Medium abgedeckt |
| Impeller | Vortex impeller, GFK |
| Motor housing | Grey cast iron |
| Pump housing | Grey cast iron |
| Submersible | Yes |
| Pressure outlet | DN 40 |
| Tank capacity | 117 l |
| Weight | 50 kg |
| Electrical data | |
|---|---|
| Voltage | 1/N/PE~230 V |
| Motor rating P1 | 1.7 kW |
| Motor rating P2 | 1.14 kW |
| Current | 7.5 A |
| Wires | 6G1,5 |
| Type of enclosure | IP 68 |
| Insulation class | F |
| Winding thermostat | Yes |
| Plug | Safety |
| Performance | |||||||
|---|---|---|---|---|---|---|---|
| Delivery head H [m] | 2 | 4 | 6 | 8 | 10 | 12 | 14 |
| Flow rate Q [m³/h] | 17 | 16 | 14 | 12 | 9 | 7 | 4 |
Specifications can be changed without notice. Performance subject to ISO 9906 tolerances.
The minimum flow velocity in the pressure piping must be 0.7 m/s according to EN 12056.
This data is represented in the performance curve as a limit of application.
Dimensions compli 100 M (mm)
Dimensions compli 500 M (mm)
Dimensions compli 1000 M (mm)
Example of installation compli 100
Example of installation compli 500 / 1000
Example of installation compli 1000
| Mechanical accessory | ||||||
|---|---|---|---|---|---|---|
| Code No. | ||||||
| Inlet gate valve PVC | ||||||
| with two pipe sockets, DN 150, PN2.5 | 660x450 (HxW) | JP28591 | ||||
| Stop valve | ||||||
| brass, 1½“ (DN 40), PN 16 | 125x60 (HxB) | JP44786 | ||||
| Hand diaphragm pump | ||||||
| for emergency purposes (up to Hgeo 15 m) | 640x1½” (HxD) | JP00255 | ||||
| Elastic connection | ||||||
| + Hose band clamps, 1½“ (DN 40), PN 4 | 120x50 (HxD) | JP50902 | ||||
| Closing set | ||||||
| DN 150, required for lateral connection | JP43156 | |||||
| Electrical accessory | ||||||
|---|---|---|---|---|---|---|
| Code No. | ||||||
| Rechargeable battery | ||||||
| 9 V, for mains independent alarm | JP44850 | |||||
| Seal leak detector | ||||||
| DKG (für die Ölkammer) | JP44900 | |||||
| Smart Home | ||||||
| FTJP radio transmitter | JP47209 | |||||