UV 305-1 S
JP48693| Mechanical data | |
|---|---|
| Pump | Vertical single-stage |
| Free passage | 10 mm |
| Bearing | Ball bearings, grease-lubricated |
| Seal on motor side | Mechanical seal |
| Oil chamber | Yes |
| Seal on medium side | SiC mechanical seal |
| Run dry protection | Yes |
| Shaft | Stainless steel |
| Impeller | Stainless steel |
| Motor housing | Stainless steel |
| Submersible | Yes |
| Pressure outlet | IG 1 1/2" |
| Weight | 18 kg |
| Electrical data | |
|---|---|
| Ciruit | With built-in level control |
| Voltage | 1/N/PE~230 V |
| Motor rating P1 | 1.15 kW |
| Motor rating P2 | 0.88 kW |
| Current | 5.3 A |
| Power line | 10m H07RN8-F |
| Wires | 3G1,0 |
| Type of enclosure | IP 68 |
| Insulation class | F |
| Winding thermostat | Yes |
| Motor protection | Integrated |
| Plug | Safety |
| Performance | ||||
|---|---|---|---|---|
| Delivery head H [m] | 1 | 3 | 5 | 7 |
| Flow rate Q [m³/h] | 21 | 17.5 | 14 | 7 |
Specifications can be changed without notice. Performance subject to ISO 9906 tolerances.
The minimum flow velocity in the pressure piping must be 0.7 m/s according to EN 12056.
This data is represented in the performance curve as a limit of application.
Single unit: sump area 40x50 cm
Duplex unit: sump min. 40x70 cm
In case of installation beneath the backpressure level the pressure tube must be taken in a loop over the local backup level acc. to EN 12056. Besides, it must be secured with an EN 12050-4-proofed swing-type check valve. Additionally we recommend an alarm system.
In accordance with EN 12056-4 section 5.1, it has a built-in automatic spare pump or a double attachment included, which ensures that sewage drainage is not interrupted.
Suspend control unit in a dry room
| Mechanical accessory | ||||||
|---|---|---|---|---|---|---|
| Code No. | ||||||
| Swing-type check valve | ||||||
| R40 EN 12050-4 | 1½“ (DN 40), PN 4 | 150x120 (HxB) | JP00317 | |||
| DR 40 EN 12050-4 | 1½“ (DN 40), PN 4 | 200x280 (HxB) | JP09155 | |||
| Stop valve | ||||||
| brass, 1½“ (DN 40), PN 16 | 125x60 (HxB) | JP44786 | ||||
| Elastic connection | ||||||
| + Hose band clamps, 1½“ (DN 40), PN 4 | 120x50 (HxD) | JP50902 | ||||
| Hose coupling | ||||||
| Coupling Storz C | 1½“ male thread | JP44770 | ||||
| Coupling wrench | JP25708 | |||||
| Pressure hose | ||||||
| 12,5 m, synthetic, with coupling Storz C, Ø 38 mm | JP50298 | |||||
| 15 m, synthetic, with coupling Storz C, Ø 52 mm | JP00336 | |||||
| Chain | ||||||
| certified, 2.5 m, 320 kg, 5 rings (EN 818 mod.) | JP45901 | |||||
| certified, 5.0 m, 320 kg, 8 rings (EN 818 mod.) | JP45902 | |||||
| certified, 7.5 m, 320 kg, 11 rings (EN 818 mod.) | JP47365 | |||||
| Shackle, certified, 630 kg, stainless steel | JP45904 | |||||
| Electrical accessory | ||||||
|---|---|---|---|---|---|---|
| Code No. | ||||||
| Alarm unit | ||||||
| AG10 | subm. ball contact switch, mains dependent, potential-free contact, 9.5 m cable | JP44892 | ||||
| Level control | ||||||
| Weight | to stabilize the subm. ball contact switch | JP44803 | ||||
| Rechargeable battery | ||||||
| 9 V, for mains independent alarm | JP44850 | |||||