Control units and components
HighLogo LC-Sets incl. outdoor cabinet
USER-FRIENDLY MICROPROCESSOR CONTROLS UNITS AS SETS INCL. TYPE A OUTDOOR CABINET FOR EXPLOSION-PROOF WASTE WATER PUMPS UP TO 4 KW CONNECTED LOAD
HighLogo-Steuerungen inkl. Außenschrank Typ A als Sets, komplett vormontiert.
Zeitersparnis bei der Installation
- HighLogo control units incl. outdoor cabinet Typ A as sets
- Completely pre-assembled
- Time saving during installation
- Large backlit clear text display
- Start-up assistant
- Multilingual
The HighLogo LCX and LCSX microprocessor control units have been developed as practical sets with a type A outdoor cabinet for easy installation. The controL units monitor and control one or two sewage pumps, depending on the water level, with or without explosion proof.
The operating status of the pump station is shown on a graphic display and additional LEDs. Operation is simple using a multifunction knob and a push-button. The operating hours, switch-on cycles of the pump(s), power consumption, any fault messages and maintenance reminders can be called up in the multilingual menu. An integrated event memory enables additional diagnostics. Faults and flood alarms are shown on the display and signalled by an alarm buzzer and a flashing light and can be forwarded via potential-free contacts. In the event of a power failure, an optional 9V rechargeable battery (accessory) can signal a flood alarm independently of the mains supply.
For pressure drainage systems or sewage pumps in sumps up to Ø 1.5 m, the HighLogo control units are equipped with a back pressure level system as standard. Two integrated pressure switches are connected via air tubes (accessories) to the open pressure bells suspended in the pump sump. This 2-circuit system offers additional safety in the event of flooding. The dry-running protection switch (TLS) available as an accessory, together with the mechanical overcurrent release and runtime monitoring, fulfils the requirements of the ATEX directive for explosion protection (ATEX mode can be selected via the menu).
Further accessories are available on request.
Plastic outdoor cabinet type A incl. HighLogo control unit ...LCX ...LCSX, flashing light, lock and sealing plug.
12 results
Type | Code No. | Motor protection | Pre-fuse | Automatic alternate operation | Motor protection typ | Peak load operation | Type | Main switch |
---|---|---|---|---|---|---|---|---|
JP50850 | 2.4 ... 4 A | 16 A | No | Overload rely | No | Single units with pressure switches, without tube set and DRP | No | |
JP50851 | 4 ... 6 A | 16 A | No | Overload rely | No | Single units with pressure switches, without tube set and DRP | No | |
JP50852 | 6 ... 9 A | 16 A | No | Overload rely | No | Single units with pressure switches, without tube set and DRP | No | |
JP50853 | 2.5 ... 4 A | 16 A | Yes | Motor protection switch | Yes | Duplex units with pressure switches, without tube set and DRP | No | |
JP50854 | 4 ... 6.3 A | 20 A | Yes | Motor protection switch | Yes | Duplex units with pressure switches, without tube set and DRP | No | |
JP50855 | 6.3 ... 10 A | 25 A | Yes | Motor protection switch | Yes | Duplex units with pressure switches, without tube set and DRP | No | |
JP50856 | 2.4 ... 4 A | 16 A | No | Overload rely | No | Single units with pressure switches, without tube set and DRP, with main switch | Yes | |
JP50857 | 4 ... 6 A | 16 A | No | Overload rely | No | Single units with pressure switches, without tube set and DRP, with main switch | Yes | |
JP50858 | 6 ... 9 A | 16 A | No | Overload rely | No | Single units with pressure switches, without tube set and DRP, with main switch | Yes | |
JP50859 | 2.5 ... 4 A | 16 A | Yes | Motor protection switch | Yes | Duplex units with pressure switches, without tube set and DRP, with main switch | Yes | |
JP50860 | 4 ... 6.3 A | 20 A | Yes | Motor protection switch | Yes | Duplex units with pressure switches, without tube set and DRP, with main switch | Yes | |
JP50861 | 6.3 ... 10 A | 25 A | Yes | Motor protection switch | Yes | Duplex units with pressure switches, without tube set and DRP, with main switch | Yes |