Mechanical data
Pump
Vertical single-stage
Free passage
50 mm
Pressure pipe
DN 80
Shaft
Stainless steel
Impeller
Vortex impeller, stainless steel
Motor housing
Stainless steel
Pump housing
Plastic, grey cast iron
Submersible
Yes
Pressure outlet
DN 80
Tank capacity
90 l
Weight
65 kg
Electrical data
Voltage
1/N/PE~230 V
Motor rating P1
1.2 kW
Motor rating P2
0.98 kW
Current
4.5 A
Power line
4m H07RN-F
Wires
4G1,0
Type of enclosure
IP 68
Insulation class
F
Winding thermostat
Yes
Plug
Safety
Performance
Delivery head H [m] 123456
Flow rate Q [m³/h] 302622191511

Specifications can be changed without notice. Performance subject to ISO 9906 tolerances.

The minimum flow velocity in the pressure piping must be 0.7 m/s according to EN 12056.
This data is represented in the performance curve as a limit of application.

Dimensions with swing-type check valve (mm)
Example of installation
Example of installation

The compli has a DN 80/PN 4 outlet flange. The following stop valve and pipework are installed in DN 80.
In keeping with the construction and testing principles of European standard EN 12050, sewage lifting stations are to be used for the transport of faecal matter and domestic wastewater in building drainage systems as described in German standard DIN 1986 T3. In keeping with the stipulations of European standard EN 12056-4 they have to be mounted with collecting tanks inside building permitting a free space of 60 cm for operation and repair. The pressure pipe has to be passed above the locally defined backpressure level and a non-return valve tested in keeping with European standard 12050-4 has to be mounted. In keeping with European standard 12056 the ventilation pipe has to be passed up to the roof.

Attention! The inlet pipes of the lowlateral inlets must be euipped with a dam loop. This loop must have at least a height of 180 mm between ground and invert. The feed line must be ventilated on its highest elevation.

Mechanical accessory
Code No.
1
Inlet gate valve PVC
with two pipe sockets, DN 100, PN1 360x295 (HxW) JP28297
2
Sluice valve
DN 80, PN 10, EN 1171 315x180 (HxB) JP00639
3
Connection for emergency dewatering
with stop valve and hose connection 1“, 1¼“ and 1½“ JP49138
Hand diaphragm pump
for emergency purposes (up to H geod 15 m) 640x1½” (HxD) JP00255
4
Stop valve
brass, 1½“ (DN 40), PN 16 125x60 (HxB) JP44786
5
Elastic connection
1½“ (DN 40), PN 4 120x50 (HxD) JP44777
6
Hose band clamp
1½“ JP44763
7
Adapter ring
DN 80-DN 80 SML JP50173
8
Connection kit
DN 100 D=110 JP42910
9
Closing set
DN 100, required for lateral connection JP50172
Electrical accessory
Code No.
a
Rechargeable battery
9 V, for mains independent alarm JP44850
b
Smart Home
FTJP radio transmitter JP47209

Always well informed!